Hamada Boiler continues to develop small and medium size of Fluidized Bed Boiler to meet requirement of many industries in the region. DF series use the most popular model "D" boiler body as a main pressure vessel so that the common spare parts with widely distributed D model will make maintenance easy. Moreover, all D-model already operating in many countries whether fixed grate type or chain travelling grate type can be converted to DF model by constructing fluidized bed combustion chamber just below the main D model boiler body and connect the two components by up going tube and down commer tube. In fact, to date, many chain grate D model boilers have been converted to fluidized bed system in Indonesia.

Boiler
Delivery of DF-16t Boiler by low bed trailer to PT. SRITEX, Solo

2 units of DF-22, 22 ton 25 Kg/cm2 pressure Fluidized Bed Coal Boiler at TEIJIN INDONESIA FIBER(TIFICO), Tangerang
Specification Unit DF-10-16 DF-15-16
Rated Evaporation
kg./hr.
10000
15000
Working Pressure
MPa
1.6
1.6
Steam temperature
°C
204
204
FBC effective heating surface
m2
12.15
18.43
Expanded zone heating area
m2
33.61
39.27
Convection tube heating area
m2
217.92
274.09
Economizer heating area
m2
174.4
218
Superheater heating area
m2
option
option
Air preheater heating area
m2
option
option
Total effective heating area
m2
438.08
549.79
FBC base plate area
m2
3.105
4.65
No. of air nozzle
pcs.
648
1026
Air hole opening ratio
0
2.55
2.72
Height of overflow
mm
1050
1040
FBC area dimension
mm
1350x2300
1660x2800
Expanded zone dimension
m2
2100x2980
2400x3400
Expanded zone volume
m3
27.67
37.63
Fluidizing temperature
°C
956
972
Fluidizing hot air speed
m/s
3.4
3.2
Fluidizing cold air speed
m/s
0.84
0.79
Critical air speed
m/s
1.209
1.22
Fluidizing factor
N
2.812
2.63
E. zone outlet temperature
°C
784.77
823.9
Forced draft fan :

Model

9-26 No.6.3 R0
9-19, No.12.5D R0

Capacity

m3/hr.

Static Pressure

Pa
Q=11809 H=9340
Q=18448 H=9520

Electric motor

kw
55
75
Overfire Draft Fan :

Model

9-19 No.5A
9-19 No.5A

Capacity

m3

Static Pressure

Pa
Q=2737 H=5770
Q=2737 H=5770

Electric Motor

kw
7.5
7.5
Induced Draft Fan :

Model

GY10-11 10D L45
Y5-47 No.12D

Capacity

m3

Static Pressure

Pa
Q=30000 H=3185
Q=46000 H=3577

Electric Motor

kw
45
75
Feedwater Pump :

Model

2-1/2GC-6x7
2-1/2GC-6x8

Capacity

m3

Static Pressure

MPa
Q=15 H=2.12
Q=20 H=2.16

Electric Motor

kw
30
30
Steam water pump :

Model

QB-4
QB-5

Capacity

m3/hr.
Q=4-9
Q=5-13
 